urunler

UMH 05 With Double Seperatör & Circuit Breaker Busbar Connection (Coupling) Cubicle

Features

L.V panel partition
Measuring Current Transformer
Cover front
Capacitive voltage divider insulator
Main bar
SF6 gas  disconnector
Circuit Breaker
Circuit Breaker Mechanism
Protection current transformer

 

Technical Specifications

 

 

TECHNICAL SPECIFICATIONS OF PRODUCTS

PRODUCT BUSBAR CONNECTING (COUPLING) SWITCHGEAR
PRODUCT CODE UMH 24-05
PRODUCT TYPE 24 kV / 630-1250A / 16-25 kA
TESTING LABORATORY ICMET
POWER FREQUENCY WITHSTAND VOLTAGE 50kV
POWER FREQUENCY WITHSTAND VOLTAGE ACROOSS THE ISOLATING DISTANCE 60 kV
RATED LIGHTING IMPULS WITHSTAND  VOLTAGE 125 kV
RATED LIGHTING IMPULS WITHSTAND  VOLTAGE ACROSS THE ISOLATING DISTANCE 140 kV
PRODUCT DIMENSIONS 1000X1000X1700 mm
INTERNAL ARC CLASS & INTERNAL ARC CURRENT AFL  25kA 1s
DEGREE OF PROTECTION IP 3X
MAIN CONDUCTING BAR Ø 40×30 mm
EARTHING BAR 40×5 mm
INSULATOR 24 kV 1000 N
NET WEIGHT OF PRODUCT 500 kg

 

EARTHING SWITCH

TYPE MST 24kV 25 kA Clas E2

SF6 GAS CIRCUIT BREAKER

TYPE BGK 24 125 25 36 kV / 630-1250A / 16-25 kA
GAS PRESSURE 2 bar

SF6 LOAD BREAK SWITCH

TYPE BNA 24 125 25 24 kV / 630-1250A  / 16-25 kA
GAS PRESSURE 1,5 bar

CURRENT TRANSFORMER

TYPE 24 kV100 In15va 600-5A

{/tabs
}

sertifikalar