urunler

UMH 03 Voltage Measurement Cubicle

Features

L.V panel partition
SF6 gas load disconnector
M.V. fuse
Grounding system
Voltage transformer

 

Technical Specifications

 

 

TECHNICAL SPECIFICATIONS OF PRODUCTS

PRODUCT VOLTAGE TRANSFORMER SWITCHGEAR
PRODUCT CODE UMH 24-03
PRODUCT TYPE 24kV / 630-1250A / 16-25kA
TESTING LABORATORY ICMET
POWER FREQUENCY WITHSTAND VOLTAGE 50kV
POWER FREQUENCY WITHSTAND VOLTAGE ACROOSS THE ISOLATING DISTANCE 60kV
RATED LIGHTING IMPULS WITHSTAND  VOLTAGE 125kV
RATED LIGHTING IMPULS WITHSTAND  VOLTAGE ACROSS THE ISOLATING DISTANCE 140kV
PRODUCT DIMENSIONS 500X1000X1700 mm
INTERNAL ARC CLASS & INTERNAL ARC CURRENT AFL 25kA 1s
DEGREE OF PROTECTION IP 3X
MAIN CONDUCTING BAR Ø 40×30 mm
EARTHING BAR 40×5 mm
INSULATOR 24kV 1000 N
NET WEIGHT OF PRODUCT 350 kg

 

EARTHING SWITCH

TYPE MST 24kV 25kA

Clas E2

SF6 LOAD BREAK SWITCH

TYPE BNA 24 125 25

24 Kv / 630-1250A / 16-25kA

GAS PRESSURE 1,5 bar

VOLTAGE TRANSFORMER

TYPE 24 Kv / 3-0.1 kV/360 va cl0.5

HIGH VOLTAGE FUSE

TYPE 24 kV   max 63A

 

 

 
 

sertifikalar