urunler

UMH 08 Current & Voltage Measurement Cubicle

Features

L.V panel partition
Load disconnector operating mechanism
Cover front
Gate insulator
Main bar
SF6 gas load disconnector
Measurement current transformer
M.V. fuse
Area the corrective
Voltage transformer

 

Technical Specifications

 

TECHNICAL SPECIFICATIONS OF PRODUCTS

PRODUCT CURRENT AND VOLTAGE MEASUREMENT CUBICLE WITH LOAD BREAK SWITCH
PRODUCT CODE UMH 36-08
PRODUCT TYPE 36kV / 630A / 16kA
TESTING LABORATORY ICMET
PRODUCT DIMENSIONS 1000X1400X2250 mm
POWER FREQUENCY WITHSTAND VOLTAGE 70kV
POWER FREQUENCY WITHSTAND VOLTAGE ACROOSS THE ISOLATING DISTANCE 80kV
RATED LIGHTING IMPULS WITHSTAND  VOLTAGE 170kV
RATED LIGHTING IMPULS WITHSTAND  VOLTAGE ACROSS THE ISOLATING DISTANCE 195kV
DIMENSIONS AFL  16kA 1s
DEGREE OF PROTECTION IP 3X
MAIN CONDUCTING BAR 40×5 mm
EARTHING BAR 30×3 mm
INSULATOR TYPE 36 kv 500 N
NET WEIGHT OF PRODUCT 650 kg

 

 EARTHING SWITCH (16 KA)

TYPE BTA536kV 16kA  ClasE2

SF6 LOAD BREAK SWITCH

TYPE BYA 36 63 16
GAS PRESSURE 1,5  bar

CURRENT TRANSFORMER

TYPE 36kV 100 ın 15va 600-5A

VOLTAGE  TRANSFORMER

TYPE 36Kv/3-0.1 kV/360 va cl0.5

 

{/tabs
}

sertifikalar