TECHNICAL SPECIFICATIONS OF PRODUCTS 

 

PRODUCT VOLTAGE TRANSFORMER SWITCHGEAR
PRODUCT CODE UMH 36-03
PRODUCT TYPE 36kV / 630A / 16kA
TESTING LABORATORY ICMET
POWER FREQUENCY WITHSTAND VOLTAGE 70kV
POWER FREQUENCY WITHSTAND VOLTAGE ACROOSS THE ISOLATING DISTANCE 80kV
RATED LIGHTING IMPULS WITHSTAND  VOLTAGE 170kV
RATED LIGHTING IMPULS WITHSTAND  VOLTAGE ACROSS THE ISOLATING DISTANCE 195kV
PRODUCT DIMENSIONS 750X1400X2250 mm
INTERNAL ARC CLASS & INTERNAL ARC CURRENT AFL 16kA 1s
DEGREE OF PROTECTION IP 3X
MAIN CONDUCTING BAR 40×5 mm
EARTHING BAR 30×3 mm
INSULATOR 36kV 500 N
NET WEIGHT OF PRODUCT 350 kg

 

EARTHING SWITCH

TYPE BTA536kV 16kA  ClasE2

SF6 LOAD BREAK SWITCH

TYPE BNA 36 63 1636kV 630A 16kA
GAS PRESSURE 1,5 bar

VOLTAGE TRANSFORMER

TYPE 36Kv / 3-0.1 kV/360 va cl0.5

HIGH VOLTAGE FUSE

TYPE 36kV   max. 63A

 

 

 

 
 